Analysis of load transfer on radial distribution systems with tie lines

Chien Hsing Lee, Chi Ming Huang

Research output: Contribution to journalArticlepeer-review

8 Citations (Scopus)

Abstract

This paper analyzes four types of load transfer in the radial distribution system with tie lines of Taiwan power company (TPC). Type I is the two feeders tied and were fed by the same transformer located in the same secondary substation. Type II is the two feeders tied and were fed by two different transformers located in the same secondary substation. Type III is the two feeders tied and were fed by two different transformers located in different secondary substations. Type IV is the two feeders tied and were fed by two different transformers, one is located in a distribution substation and the other is located in a secondary substation. The test results are recorded and summarized to determine the effective scheme of load transfer without power interruptions. As a result, Type I is the most simple method to eliminate customers' interruption during load transfer.

Original languageEnglish
Pages (from-to)268-284
Number of pages17
JournalEuropean Transactions on Electrical Power
Volume17
Issue number3
DOIs
Publication statusPublished - 2007 May

All Science Journal Classification (ASJC) codes

  • Energy Engineering and Power Technology
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Analysis of load transfer on radial distribution systems with tie lines'. Together they form a unique fingerprint.