Performance of a vortex flowmeter downstream of elbows

Jiun-Jih Miau, S. M. Lin, C. C. Hu, Jung-Hua Chou

Research output: Chapter in Book/Report/Conference proceedingChapter

Abstract

Installation effects concerning two cases of single elbow and double elbows out-of-plane situated upstream of a vortex flowmeter were studied. The performance of the vortex flowmeter was examined in terms of the shift in Strouhal number, the linearity of Strouhal number and the signal quality defined. Interestingly noted is that in each of the cases studied the quality of the meter signals obtained at 15 to 25 pipe diameters downstream of the elbow(s) can be even better than that obtained in the fully-developed region. This enlightens that one can take advantage of this characteristic in determining the meter location.

Original languageEnglish
Title of host publicationProceedings of the 1999 3rd ASME/JSME Joint Fluids Engineering Conference, FEDSM'99, San Francisco, California, USA, 18-23 July 1999 (CD-ROM)
PublisherAmerican Society of Mechanical Engineers
Number of pages1
ISBN (Print)0791819612
Publication statusPublished - 1999

All Science Journal Classification (ASJC) codes

  • Earth and Planetary Sciences(all)
  • Engineering(all)
  • Environmental Science(all)

Fingerprint Dive into the research topics of 'Performance of a vortex flowmeter downstream of elbows'. Together they form a unique fingerprint.

Cite this