摘要
Three-phase Transformers are key equipments in power systems and power plants. Security and stability of three-phase transformers are both important and necessary to system operation. When a three-phase transformer is energized, the inrush current due to flux saturation in the core results in a malfunction of the differential relay and also causes a stress impact to the transformer. These have a bad effect on the security and stability of power system. In this paper, an optimum non-synchronous switching-on suppressing method of three-phase transformers inrush current is proposed. The proposed method is examined by experiment. It has excellent performance for suppressing three-phase inrush current. It is applied to design the protective system of a three-phase transformer. For the optimum non-synchronous switching-on suppressing method, a protective system based on a single-chip controller is implemented. The system can distinguish fault current from inrush current. Therefore stress impact and overvoltage resulting from three-phase inrush current can be avoided. The active protection of three-phase transformer is obtained to improve the protective relaying system. Now, problems caused by three-phase inrush current can be detected and solved effectively.
原文 | English |
---|---|
頁面 | 1808-1813 |
頁數 | 6 |
出版狀態 | Published - 2002 |
事件 | IEEE/PES Transmission and Distribution Conference and Exhibition 2002 : Asia Pacific - Yokahama, Japan 持續時間: 2002 10月 6 → 2002 10月 10 |
Other
Other | IEEE/PES Transmission and Distribution Conference and Exhibition 2002 : Asia Pacific |
---|---|
國家/地區 | Japan |
城市 | Yokahama |
期間 | 02-10-06 → 02-10-10 |
All Science Journal Classification (ASJC) codes
- 電氣與電子工程