A performance study of PEMS applied to the Hsinta power station of Taipower

T. W. Chien, H. Chu, W. C. Hsu, Y. Y. Tu, H. S. Tsai, K. Y. Chen

研究成果: Article同行評審

11 引文 斯高帕斯(Scopus)

摘要

Predictive emission monitoring systems (PEMS) have been shown to be a promising technology for calculating the emissions from gas-fired stationary sources. One of the first demonstration PEMS in Taiwan was installed and operated successfully at the Hsinta power plant of the Taiwan Power Company (Taipower) in 2000. To improve the accuracy of this PEMS model, further studies were conducted at the same combined cycle gas turbine (CCGT) unit #1 of the Hsinta power plant. To optimize the NO X PEMS model, several functions were progressively developed including a log model, a one-level linear model, a three-level linear model, a 15-variable linear model, and a 15-variable with start-up mode model. The latter gave the relative accuracies (RA) and correlation coefficients between PEMS and a continuous emission monitoring system (CEMS) in the range of 3.38-14.77% and 0.955-0.989, respectively, which fulfill the criteria of the USEPA draft on PEMS performance specifications. Similarly, this model demonstrated RAs for low, medium, high level, and a three-level average less than 20% which meet CEMS requirements set out by Taiwan EPA.

原文English
頁(從 - 到)223-230
頁數8
期刊Atmospheric Environment
39
發行號2
DOIs
出版狀態Published - 2005 1月

All Science Journal Classification (ASJC) codes

  • 環境科學 (全部)
  • 大氣科學

指紋

深入研究「A performance study of PEMS applied to the Hsinta power station of Taipower」主題。共同形成了獨特的指紋。

引用此