Application of an energy management system in combination with FMCS to high energy consuming IT industries of Taiwan

Shin Ku Lee, Min Cheng Teng, Kuo Shun Fan, Kuan Hsiung Yang, Richard S. Horng

研究成果: Article同行評審

29 引文 斯高帕斯(Scopus)

摘要

A commissioning unit with an energy management system (EMS) was developed to be used together with facility monitoring and control systems (FMCS). This paper describes the testing of the new coupling system, in which a detailed management program is embedded for real time control decision making. First, a survey was conducted to evaluate the current power consumption of the facility systems, and found that HVAC is the most energy intensive system. Then a case study was performed, while the plant was in operation, to demonstrate the feasibility of the new coupling system, and a 9.6% chiller efficiency increase and total 23.2% annual energy saving for the chillers were reached, by optimizing the part load ratio condition of chillers and pumps. The results from in situ experiments show that applying this energy management system to the IT industry is feasible. A better custom-made FMCS with EMS, and full scale testing to greatly increase the overall energy efficiency, is recommended.

原文English
頁(從 - 到)3060-3070
頁數11
期刊Energy Conversion and Management
52
發行號8-9
DOIs
出版狀態Published - 2011 8月

All Science Journal Classification (ASJC) codes

  • 可再生能源、永續發展與環境
  • 核能與工程
  • 燃料技術
  • 能源工程與電力技術

指紋

深入研究「Application of an energy management system in combination with FMCS to high energy consuming IT industries of Taiwan」主題。共同形成了獨特的指紋。

引用此