摘要
This paper compares subsynchronous resonance (SSR) results in two power generation systems (PGSs). One is a traditional steam turbine generator (STG) system based on a synchronous generator (SG), and the other is an offshore wind farm (OWF) system based on an equivalent aggregated doubly-fed induction generator (DFIG) driven by an equivalent aggregated wind turbine. The d-q axis equivalent-circuit models of the two PGSs under three-phase balanced loading conditions are derived to establish the complete system models, including the STG-based PGS, the DFIG-based OWF PGS, the electrical network of the IEEE Second Benchmark Model (SBM), system-1. The studied two PGSs' small-signal stability and transient simulation results are systematically performed and compared. The simulation results show that the special unstable modes in the two studied configurations can cause unstable SSR characteristics.
| 原文 | English |
|---|---|
| 主出版物標題 | 2025 IEEE Industry Applications Society Annual Meeting, IAS 2025 |
| 發行者 | Institute of Electrical and Electronics Engineers Inc. |
| ISBN(電子) | 9781665457767 |
| DOIs | |
| 出版狀態 | Published - 2025 |
| 事件 | 2025 IEEE Industry Applications Society Annual Meeting, IAS 2025 - Taipei, Taiwan 持續時間: 2025 6月 15 → 2025 6月 20 |
出版系列
| 名字 | Conference Record - IAS Annual Meeting (IEEE Industry Applications Society) |
|---|---|
| ISSN(列印) | 0197-2618 |
Conference
| Conference | 2025 IEEE Industry Applications Society Annual Meeting, IAS 2025 |
|---|---|
| 國家/地區 | Taiwan |
| 城市 | Taipei |
| 期間 | 25-06-15 → 25-06-20 |
UN SDG
此研究成果有助於以下永續發展目標
-
SDG 7 經濟實惠的清潔能源
All Science Journal Classification (ASJC) codes
- 控制與系統工程
- 工業與製造工程
- 電氣與電子工程