Comparative Thermal Performances between Pumped Thermosyphon Loops with Different Condenser Configurations Using R245fa as Working Fluid

Shyy Woei Chang, Yn An Tsai, Cheng Lin Tsai

研究成果: Article同行評審

摘要

A pumped two-phase thermosyphon loop is broadly utilized to intensify the cooling duties of electronic chipsets/systems and the effectiveness for harvesting thermal energy. The configuration of a condenser not only affects the heat transfer in the condenser, but also has an effect on the saturation pressures during the boiling and condensation processes to alter the hydrothermal performance of a pumped thermosyphon loop. The influence of the condenser configuration on the hydrothermal performance of a pumped thermosyphon loop is rarely studied. The present study comparatively examined the thermal performances of two pumped thermosyphon loops with a conventional tube-fin condenser and the expansion-tank condenser. The thermodynamic cycles in pressure-temperature and pressure-enthalpy diagrams, Nusselt numbers of evaporator and condenser, thermal resistances and various performance indexes evaluated at constant pumping powers at the controlled through-flow Reynolds numbers, boiling numbers and condenser thermal resistances were measured. At the similar thermal loads, flow rates, and fluid entry temperatures of condenser, the operating pressure of the thermosyphon loop with expansion tank condenser was considerably reduced from that with tube fin condenser, leading to the lower saturation temperature for reducing the thermal resistance and the lesser pressure drop across the loop with a noticeable hydrothermal performance improvement. At the parametric conditions tested, the ratio of dimensionless overall thermal resistances between the loops with expansion tank condenser and tube fin condenser fell in the range of 0.81–0.99. When the loop performance was compared at a constant cooling airflow rate without considering the more pumping power consumption for the loop with tube fin condenser, the ranges of thermal resistance for the loops with expansion tank condenser and tube fin condenser were 0.13–0.21 (KW−1) and 0.15–0.23 (KW−1 ). The merit indices evaluating the comparative hydrothermal performances of evaporator, condenser and loop between the two looped thermosyphons highlighted the significance of condenser design and affirmed the performance improvement by changing tube fin condenser into expansion tank condenser. The empirical correlations of evaporator Nusselt number, condenser Nus-selt number, and overall thermal resistance using Reynolds number, boiling number, and condenser thermal resistance as the controlling parameters were generated for relevant applications.

原文English
文章編號635
期刊Energies
15
發行號2
DOIs
出版狀態Published - 2022 1月 1

All Science Journal Classification (ASJC) codes

  • 可再生能源、永續發展與環境
  • 燃料技術
  • 能源工程與電力技術
  • 能源(雜項)
  • 控制和優化
  • 電氣與電子工程

指紋

深入研究「Comparative Thermal Performances between Pumped Thermosyphon Loops with Different Condenser Configurations Using R245fa as Working Fluid」主題。共同形成了獨特的指紋。

引用此