Corrosion inhibitors for the absorption refrigeration system

Ten-Chin Wen, Shih Min Lin

研究成果: Article同行評審

6 引文 斯高帕斯(Scopus)

摘要

The electrochemical polarization method was used to study the inhibitive action of LiOH, Li2CrO4, and BTA, either individually or in different combinations. Afterwards, weight-loss tests planned by orthogonal arrays were carried out to find the optimum condition for the minimum corrosion rate for copper and mild steel in LiBr solution. The results from both polarization and weight-loss tests were consistent for each other in this study. The optimum condition predicted by the orthogonal-array experiments for the minimum corrosion rate is found out by adding 1.5 g/L LiOH, 4.5 g/L Li2CrO4, and 100 mg/L BTA, whose efficiency of inhibition is about 83% for copper and 99% for mild steel.

原文English
頁(從 - 到)311-316
頁數6
期刊Journal of the Chinese Institute of Chemical Engineers
22
發行號5
出版狀態Published - 1991 9月 1

All Science Journal Classification (ASJC) codes

  • 一般化學
  • 一般化學工程

指紋

深入研究「Corrosion inhibitors for the absorption refrigeration system」主題。共同形成了獨特的指紋。

引用此