摘要
This study investigated the movable fire loads and the characteristics of combustible materials in Japanese-style wooden historical buildings via field surveys and cone calorimeter experiments. Twenty-one historical buildings with 102 rooms and a total floor area of 2235.06 m2 were surveyed to determine the movable fire load. Strong correlations among fire load density, compartment floor area, and spatial use are found in this survey. The mean values of the movable fire load density in decreasing order in terms of room use are storeroom (431.38 MJ/m2), study room (298 MJ/m2), bedroom (294.88 MJ/m2), reception room (287.20 MJ/m2), and dining room (217.11 MJ/m2), providing fire engineering design with a reliable fire load setting in various types of rooms in historical buildings.
| 原文 | English |
|---|---|
| 頁(從 - 到) | 931-942 |
| 頁數 | 12 |
| 期刊 | International Journal of Architectural Heritage |
| 卷 | 14 |
| 發行號 | 6 |
| DOIs | |
| 出版狀態 | Published - 2020 7月 2 |
UN SDG
此研究成果有助於以下永續發展目標
-
SDG 11 永續發展的城市與社群
All Science Journal Classification (ASJC) codes
- 保護
- 建築
- 視覺藝術與表演藝術
指紋
深入研究「Survey and Experimental Investigation of Movable Fire Loads in Japanese-Style Wooden Historical Buildings」主題。共同形成了獨特的指紋。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver