The study of fire resistance of building integrated photovoltaics

Ming Tsung Yang, Yu Liang Liou, Chun Kuei Chen, Hsun Ku Lee, Ta Hui Lin, Cho Fang Tsai, Ming Yuan Lei, Tien Chih Wang

研究成果: Paper同行評審

摘要

In this study, the fire and heat performance of PV modules is evaluated using the CNS 12514-1 testing method. In the test of PV module with insulation materials, there are 3 kinds of fire-resistant methods of polysilicon PV modules. Polysilicon PV modules with a calcium silicate board, a phenova insulation board, a gypsum board as exposed surfaces, respectively, were tested. There were wire holes on the back board of the PV modules in the three designs. The holes degraded fire resistance. With the aluminum and gypsum back board, the PV modules caught fire and their integrity failed. To enhance the fire and heating performance of PV modules, it is necessary to further improve the designs. The PV module with the calcium silicate board had no flames spill out during the test, but the surface temperature was higher than that of the CNS-12514-1 specification.

原文English
出版狀態Published - 2017
事件11th Asia-Pacific Conference on Combustion, ASPACC 2017 - Sydney, Australia
持續時間: 2017 十二月 102017 十二月 14

Other

Other11th Asia-Pacific Conference on Combustion, ASPACC 2017
國家/地區Australia
城市Sydney
期間17-12-1017-12-14

All Science Journal Classification (ASJC) codes

  • 凝聚態物理學
  • 能源工程與電力技術
  • 燃料技術
  • 化學工程 (全部)

指紋

深入研究「The study of fire resistance of building integrated photovoltaics」主題。共同形成了獨特的指紋。

引用此